The 13×54 water softener for hardness removal uses cation softening resin to reduce calcium and magnesium hardness. This helps limit new hardness-related scale in pipework, geysers and suitable water-using equipment.
The system combines an 13×54 FRP vessel, Runxin F64A1 manual softener valve with metal handwheel, softening resin and a brine tank. Salt-brine regeneration restores the resin for continued use.
Free salt included: One bag of softener salt is included, subject to availability.
Key Features & Benefits
-
Hardness reduction: Ion exchange targets calcium and magnesium responsible for hard water.
-
Manual regeneration: The operator turns the handwheel to select and time each stage. No electrical supply is required for the manual valve itself.
-
Regenerable resin: Suitable softener salt is used to restore the resin’s working capacity.
-
Brine tank included: Provides the separate salt-and-water reservoir used during regeneration.
-
FRP vessel: Corrosion-resistant construction houses the resin bed.
Applications
- Domestic and commercial installations with measured hard water.
- Point-of-entry softening, sized for the household or site’s peak demand.
- Reverse-osmosis pre-treatment or compatible process equipment requiring hardness reduction.
Technical Specifications
-
Product code: H2OW1513
-
Vessel size designation: 13×54; nominal vessel designation, not the installed height including the valve.
-
Vessel material: Fibreglass-reinforced plastic (FRP).
-
Treatment media: Cation softening resin
-
Head / control: Runxin F64A1 manual softener valve with metal handwheel
-
Regenerant: Water-softener salt (sodium chloride).
-
System capacity: Determined by the actual resin loading, inlet hardness, required outlet hardness and salt dose; the valve rating is not the complete system’s treatment rating.
-
Valve rated flow: 4 m³/h; hydraulic valve rating only.
-
Valve connections: DN25 inlet/outlet with nominal 1-inch female threads; nominal ½-inch male drain and ⅜-inch male brine connection.
-
Valve mounting: 2.5-inch–8 NPSM; riser outside diameter approximately 26.7 mm.
-
Valve operating range: 1.5–6 bar and 5–50 °C. The complete assembly must stay within its lowest-rated component limits.
What’s Included
-
Vessel: 1 × 13×54 FRP vessel.
-
Internals: Riser pipe and distribution strainers.
-
Control valve: 1 × Runxin F64A1 manual softener valve with metal handwheel.
-
Resin: Cation softening resin included for this product configuration.
-
Brine tank: 1 × brine tank with brine assembly.
-
Salt: 1 free bag of softener salt, subject to availability.
Installation & Use
-
Sizing and commissioning: Set treatment capacity, salt dose, stage times and regeneration interval from the water analysis and actual resin loading.
-
Pre-treatment: Provide sediment and iron/manganese treatment where necessary to protect the resin.
-
Installation: Provide suitable pipework, isolation/bypass arrangements and a drain for regeneration water. Any feed pump has its own power and installation requirements.
-
Resin loading: Allow the specified expansion space for backwashing; do not fill the vessel completely with resin.
-
Routine care: Keep the brine tank supplied with suitable salt and test treated-water hardness to confirm performance.
-
Manual stage selection: The F64A1 provides service, backwash, brine draw with slow rinse, brine refill and fast rinse positions. Follow the manufacturer’s instructions and the installer’s settings for the correct sequence and duration.
-
Operator responsibility: The valve does not measure the remaining resin capacity or initiate regeneration automatically. Select and time the stages, then return the valve to service.
Important Information
-
Water supply during regeneration: Allow for an interruption to normal softened-water service during regeneration of this single-vessel system.
-
Treatment scope: Softening reduces hardness; it does not disinfect water or replace treatment for other contaminants.
-
Existing scale: The purpose is to reduce further hardness-related scale formation, rather than promise immediate removal of established deposits.
-
Safe servicing: Isolate and depressurise before servicing. Follow the vessel, valve and resin instructions.
Downloads