The 18×65 iron and manganese removal filter uses a manganese-dioxide-coated medium to support the oxidation and filtration of iron and manganese. It can also form part of a treatment system for hydrogen sulphide, subject to water analysis and the required oxidation process.
This complete media-vessel package includes the 18×65 FRP vessel, Runxin automatic backwash valve and Katalox Light catalytic filtration media.
Key Features & Benefits
-
Targeted treatment: Helps reduce iron and manganese associated with staining and deposits in water systems.
-
Catalytic filtration: Supports the conversion and capture of dissolved contaminants when the water chemistry and oxidant conditions are suitable.
-
Downstream protection: Can reduce metal loading ahead of further filtration, softening or reverse osmosis.
-
Automatic backwash: A programmed cleaning cycle reduces hands-on valve operation. The inlet supply and waste drain must still provide the required backwash capacity.
-
FRP construction: A corrosion-resistant vessel body houses the treatment bed.
Applications
- Borehole and wellpoint water with confirmed iron or manganese contamination.
- Point-of-entry treatment and selected commercial processes, sized to the tested water quality.
- Pre-treatment ahead of downstream equipment where iron or manganese reduction is required.
Technical Specifications
-
Product code: H2OW1203
-
Vessel size designation: 18×65; nominal vessel designation, not the installed height including the valve.
-
Vessel material: Fibreglass-reinforced plastic (FRP).
-
Treatment media: Katalox Light catalytic filtration media
-
Head / control: Runxin automatic backwash valve
-
Media inlet pH range: 5.8–10.5 is the manufacturer’s media range; the required treatment pH depends on the contaminants present.
-
System design flow: Select from the water analysis, media bed depth, required outlet quality and available backwash supply. Vessel size or valve capacity alone does not establish the treatment flow.
What’s Included
-
Vessel: 1 × 18×65 FRP vessel.
-
Control valve: 1 × Runxin automatic backwash valve.
-
Media: 5 × 30 kg bags of Katalox Light media (150 kg supplied).
-
Internals: Riser pipe and distribution components as specified for this vessel.
Installation & Use
-
Before installation: Have the source water tested and confirm the treatment sequence, operating flow and backwash requirements.
-
Site connections: Arrange inlet and outlet pipework, suitable isolation/bypass provision and a correctly sized drain for backwash water.
-
Commissioning: Load and condition the media according to the media and valve instructions. Leave the required expansion space; supplied bag quantities are not an instruction to fill the vessel to the top.
-
Cleaning control: Programme the valve for the site’s water quality and follow the fitted valve instructions.
-
Operating limits: Use the lowest pressure and temperature limits of the vessel, valve and other fitted components. Isolate and depressurise before opening the vessel.
Important Information
-
Water chemistry: Confirm pH, iron, manganese, dissolved oxygen and any hydrogen sulphide before selection. Manganese treatment can need higher pH and more contact time than iron treatment.
-
Oxidation: Aeration or a controlled oxidant stage may be required. Backwashing alone does not replace the necessary oxidation conditions.
-
Media maintenance: Backwash and rinse to clear retained solids; monitor treated-water quality and pressure loss.
-